• Winner Pro Plus Rack 6KR UPS

    Input:

    • Capacity: 6000 VA / 5400 W
    • Nominal voltage: 208/220/230/240VAC
    • Voltage range: 110-300 VAC at 50% load, 176-300 VAC at 100% load
    • Frequency range: 46Hz  ~ 54Hz or 56Hz ~ 64Hz
    • Power factor: ≥ 0.99 @ nominal voltage (100% load)
      Output:
    • Output voltage: 208/220/230/240VAC   
    • Voltage regulation : ± 1%
    • Frequency range: 46Hz  ~ 54Hz or 56Hz ~ 64Hz
    • Frequency range(Batt. Mode): 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
    • Current crest ratio: 3:1
    • Harmonic distortion (Linear load): ≤ 3% THD
    • Harmonic distortion (non-linear load): ≤ 5% THD
    • Transfer time: 0 ms
    • Waveform (Batt. Mode): Pure sinewave
      Efficiency:
    • AC mode: 92% 
    • Battery mode: 90%
      Battery:
    • Battery type & number: 12 V/9 Ah 
    • Numbers: 16/20
    • Typical recharge time: 9 hours recover to 90% capacity
    • Charging current: 1A/2A (Adjustable)
      Physical:
    • Dimension: D x W x H (mm)(UPS unit): 500 x 438 x 88
    • Dimension: D x W x H (mm)(battery pack): 580x 438 x 133
    • Net weight (kgs)(UPS unit): 15
    • Net weight (kgs)(battery pack): 61
      Environment:
    • Humidity: 0-95 % RH @ 0- 40°C (non-condensing)
    • Noise level: Less than 55dBA @ 1 Meter
      Management:
    • Smart RS-232 / USB: Supports Windows®️ 2000/2003/XP/Vista/2008/Windows®️7/8, Linux, MAC
    • Optional SNMP: Power management from SNMP manager and web browser

     

  • Winner Pro Plus 3k UPS

    Input:

    • Capacity: 3000 VA / 2700 W
    • Nominal voltage: 110/115/120/127 VAC or 208/220/230/240 VAC
    • Voltage range: 60-145 VAC or 120-300 VAC at 50% load / 90-145 VAC or 180-300 VAC at 100% load
    • Frequency range: 60-70 Hz
    • Power factor: ≥ 0.99 @ nominal voltage (100% load)
      Output:
    • Output voltage: 110/115/120/127 VAC
    • Voltage regulation : ± 1%
    • Frequency range: 47-53 Hz or 57-63 Hz
    • Frequency range(Batt. Mode): 50 Hz or 60 Hz ± 0.5
    • Current crest ratio: 3:1
    • Harmonic distortion (Linear load): ≤ 3% THD
    • Harmonic distortion (non-linear load): ≤ 6% THD
    • Transfer time: 0 ms
    • Waveform (Batt. Mode): Pure sinewave
      Efficiency:
    • AC mode: 90%
    • Battery mode: 88%
      Battery:
    • Battery type & number: 12 V/9 Ah
    • Numbers: 6
    • Typical recharge time: 4 hours recover to 90% capacity
    • Charging current: 1.0A
      Physical:
    • Dimension: D x W x H (mm) (Standart model): 630 x 438 x 88
    • Dimension: D x W x H (mm) (Long run model): 460 x 438 x 88
    • Net weight (kgs)(Standart model): 29,3
    • Net weight (kgs)(Long run model): 14,2
      Environment:
    • Humidity: 20-90 % RH @ 0-40°C (Non-condensing)
    • Noise level: less than 50 dB @ 1 Meter
      Management:
    • Smart RS-232 / USB: Supports Windows®️ 2000/2003/XP/Vista/2008/Windows®️7/8, Linux, MAC
    • Optional SNMP: Power management from SNMP manager and web browser

     

  • Winner Pro Plus 2k UPS

          Input:

    • Capacity: 2000 VA / 1800 W
    • Nominal voltage: 110/115/120/127 VAC or 208/220/230/240 VAC
    • Voltage range: 60-145 VAC or 120-300 VAC at 50% load / 90-145 VAC or 180-300 VAC at 100% load
    • Frequency range: 60-70 Hz
    • Power factor: ≥ 0.99 @ nominal voltage (100% load)
      Output:
    • Output voltage: 110/115/120/127 VAC
    • Voltage regulation : ± 1%
    • Frequency range: 47-53 Hz or 57-63 Hz
    • Frequency range(Batt. Mode): 50 Hz or 60 Hz ± 0.5
    • Current crest ratio: 3:1
    • Harmonic distortion (Linear load): ≤ 3% THD
    • Harmonic distortion (non-linear load): ≤ 6% THD
    • Transfer time: 0 ms
    • Waveform (Batt. Mode): Pure sinewave
      Efficiency:
    • AC mode: 89%
    • Battery mode: 87%
      Battery:
    • Battery type & number: 12 V/9 Ah
    • Numbers: 2/3
    • Typical recharge time: 4 hours recover to 90% capacity
    • Charging current: 1.0A/2.0A (adjustable)
      Indicators:
    • LCD Panel: UPS status, load level, battery level, input/output voltage, discharge timer, fault conditions
      Alarm:
    • Battery mode: Sounding every 4 seconds
    • Low battery Sounding every second
    • Overload: Sounding every 0.5 second
    • Fault: Continuously sounding
      Physical:
    • Dimension: D x W x H (mm)(UPS unit): 421 x 190 x 318(3U)
    • Dimension: D x W x H (mm)(battery pack): 580 x 438 x 133(3U)
    • Net weight (kgs)(UPS unit): 26.2
    • Net weight (kgs)(battery pack): 6.8
      Environment:
    • Humidity: 20-90 % RH @ 0-40°C (Non-condensing)
    • Noise level: less than 50 dB
      Management:
    • Smart RS-232 / USB: Supports Windows®️ 2000/2003/XP/Vista/2008/Windows®️7/8, Linux, MAC
    • Optional SNMP: Power management from SNMP manager and web browser

     

  • Galleon 3P-10K-80K-Family UPS

     

    Input:

    • Capacity: 10000 VA / 9000 W
    • Nominal Voltage: 3×400 VAC (3Ph+N)
    • Frequency range: 46-54 Hz or 56-64 Hz

     

    Output:

    • Output voltage: 208/220/230/240 VAC
    • AC voltage regulation (Batt. Mode): ± 1%
    • Frequency range (Batt. Mode):46-54 Hz or 56-64 Hz
    • Current crest ratio: 3:1 (max.)
    • Waveform (Batt. Mode): Pure sinewave

     

    Battery:

    • Battery type: 12 V/7 Ah
    • Typical recharge time: 9 hours recover to 90% capacity
    • Charging Voltage: 273 VDC ± 1% (Based on 20pcs batteries)

     

    Indicators:

    • LCD Display: UPS status, Load level, Input/Output voltage, Discharge timer, and Fault conditions 

     

    Alarm:

    • Battery mode: Sounding every 4 seconds
    • Low battery Sounding every second
    • Overload: Sounding twice every second
    • Fault: Continuously sounding

     

    Physical:

    • Dimension: D x W x H (mm): 592x250x576
    • Net weight (kgs): 83

     

  • Winner Pro Plus 6K(L) UPS

    Input:

    • Capacity: 6000VA / 5400W 6K(L), 10000 VA / 9000 W 10K(L)
    • Nominal voltage: 208/220/230/240 VAC
    • Voltage range: 110-300 VAC at 50% load or 176-300 VAC 100% load
    • Frequency range: 46~54 Hz or 56~64 Hz
    • Power factor: ≥ 0.99 @ nominal voltage (100% load)
      Output:
    • Output voltage: 208/220/230/240 VAC  
    • Voltage regulation : ± 1%
    • Frequency range: 46~54 Hz or 56~64 Hz
    • Frequency range(Batt. Mode): 50 Hz or 60Hz ± 0.1 Hz
    • Current crest ratio: 3:1
    • Harmonic distortion (Linear load): ≤ 3% THD
    • Harmonic distortion (non-linear load): ≤ 5% THD
    • Transfer time: 0 ms
    • Waveform (Batt. Mode): Pure sinewave
      Efficiency:
    • AC mode: 92% 6K(L), 93% 10K(L)
    • Battery mode: 90% 6K(L), 91% 10K(L)
      Battery:
    • Battery type & number: 12 V/9 Ah 
    • Numbers: 16/20
    • Typical recharge time: 9 hours recover to 90% capacity
    • Charging current: 1A/2A (adjustable)
      Indicators:
    • LCD Panel: UPS status, load level, battery level, input/output voltage, discharge timer, fault conditions
      Alarm:
    • Battery mode: Sounding every 4 seconds
    • Low battery Sounding every second
    • Overload: Sounding every 0.5 second
    • Fault: Continuously sounding
      Physical:
    • Dimension: D x W x H (mm)(UPS unit): 369 x 190 x 688  6K(L), 442 x 190 x 688 10K(L)
    • Dimension: D x W x H (mm)(battery pack): 369 x 190 x 318 6K(L), 442 x 190 x 318 10K(L) 
    • Net weight (kgs)(UPS unit): 61 6K(L), 74 10K(L)
    • Net weight (kgs)(battery pack): 12 6K(L), 16 10K(L)
      Environment:
    • Humidity: 0-95 % RH @ 0-50°C (Non-condensing) 6K(L),  0-95 % RH @ 0-50°C (Non-condensing) 10K(L)
    • Noise level: less than 55 dB 6K(L),  less than 55 dB 10K(L)
      Management:
    • Smart RS-232 / USB: Supports Windows®️ 2000/2003/XP/Vista/2008/Windows®️7/8, Linux, MAC
    • Optional SNMP: Power management from SNMP manager and web browser

     

  • Winner Pro Plus-Rack 3K-ZR6-R UPS

    Input:

    • Capacity: 3000 VA / 2700 W
    • Nominal voltage: 110/115/120/127VAC or 208/220/230/240VAC
    • Voltage range:  60-145 VAC  or 120-300 VAC at 50% load, 90-145 VAC or 180-300 VAC at 100% load
    • Frequency range: 40Hz  ~ 70 Hz
    • Power factor: ≥ 0.99 @ nominal voltage (100% load)
      Output:
    • Output voltage: 110/115/120/127VAC or 208/220/230/240VAC   
    • Voltage regulation : ± 1%
    • Frequency range: 47~ 53 Hz or 57 ~ 63 Hz
    • Frequency range(Batt. Mode): 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
    • Current crest ratio: 3:1
    • Harmonic distortion (Linear load): ≤ 3% THD
    • Harmonic distortion (non-linear load): ≤ 6% THD
    • Transfer time: 0 ms
    • Waveform (Batt. Mode): Pure sinewave
      Efficiency:
    • AC mode: 90% 
    • Battery mode: 88%
      Battery:
    • Battery type & number: 12 V/9 Ah 
    • Numbers: 6
    • Typical recharge time: 4 hours recover to 90% capacity
    • Charging current: 1.0A
      Physical:
    • Dimension: D x W x H (mm)(UPS unit): 630 x 438 x 88
    • Dimension: D x W x H (mm)(battery pack): 630 x 438 x 88
    • Net weight (kgs)(UPS unit): 29.3
    • Net weight (kgs)(battery pack): 14.2
      Environment:
    • Humidity: 20-90 % RH @ 0- 40°C (non-condensing)
    • Noise level: Less than 50dBA @ 1 Meter
      Management:
    • Smart RS-232 / USB: Supports Windows®️ 2000/2003/XP/Vista/2008/Windows®️7/8, Linux, MAC
    • Optional SNMP: Power management from SNMP manager and web browser

     

  • Winner Pro 10K(L) Online UPS

    Input:

    • Capacity: 10000 VA / 8000 W
    • Voltage: 208/220/230/240 VAC
    • Voltage range: 110-300 VAC ± 3% at 50% load / 176-300 VAC ± 3% at 100% load
    • Frequency range: 46~54 or 56~64 Hz
    • Power factor: ≥ 0.99 @ nominal voltage (100% load)
      Output:
    • Output voltage: 208/220/230/240 VAC
    • Voltage regulation : ± 1%
    • Frequency range: 46~54 or 56~64 Hz
    • Frequency range(Batt. Mode): 50 Hz ±0.1 Hz or 60 Hz ±0.1 Hz
    • Current crest ratio: 3:1
    • Harmonic distortion(Linear load): ≤ 3% THD
    • Harmonic distortion(non-linear load): ≤ 5% THD
    • Transfer time: 0 ms
    • Waveform (Batt. Mode): pure sinewave
      Efficiency:
    • AC mode: 93%
    • Battery mode: 91%
      Battery:
    • Battery type & number: 12 V/9 Ah
    • Numbers:16/20
    • Typical recharge time: 9 hours recover to 90% capacity
    • Charging current: 1A/2A (adjustable)
      Indicators:
    • LCD Panel: UPS status, load level, battery level, input/output voltage, discharge timer, fault conditions
      Alarm:
    • Battery mode: Sounding every 4 seconds
    • Low battery Sounding every second
    • Overload: Sounding every 0.5 second
    • Fault: Continuously sounding
      Physical:
    • Dimension: D x W x H (mm)(UPS unit): 580 x 438 x 133(3U)
    • Dimension: D x W x H (mm)(battery pack): 580 x 438 x 133(3U)
    • Net weight (kgs)(UPS unit): 18
    • Net weight (kgs)(battery pack): 61
      Environment:
    • Humidity: 0-95 % RH @ 0-40°C (non-condensing)
    • Noise level: less than 58 dB
      Management:
    • Smart RS-232 / USB: Supports Windows®️ 2000/2003/XP/Vista/2008/Windows®️7/8, Linux, MAC
    • Optional SNMP: Power management from SNMP manager and web browser