| Power Factor |
0.99 @ Nominall Voltage (100% load) |
| OUTPUT |
| Output Voltage |
110/115/120/127VAC or 208/220/230/240VAC |
| Voltage Regulation |
± 1 % |
| Frequency Range (Synchronized Range) |
47~ 53 Hz or 57 ~ 63 Hz |
| Frequency Range (Batt. Mode) |
50 Hz or 60 Hz ± 0.5% |
| Current Crest Ratio |
3:1 |
| Harmonic Distortion |
3% THD (Linear Load)
6% THD (Non-linear Load) |
| Transfer Time |
AC Mode to Battery Mode |
Zero |
| Inverter to Bypass |
4 ms (Typical) |
| Waveform (Batt. Mode) |
Pure Sinewave |
| EFFICIENCY |
| AC Mode |
88% |
| Battery Mode |
83% |
| BATTERY |
| Standard Model |
Battery Type |
12 V / 9 Ah |
| Numbers |
2 |
3 |
| Typical Recharge Ti me |
4 hours recover to 90% capacity |
| Charging Current ( max.) |
1A |
| Charging Voltage |
27.4VDC ± 1% |
41.0VDC ± 1% |
|
Battery Type |
Depending on applications |
|
Numbers |
3 |
| Long-run Model ** |
Charging Current ( max.) |
1.0A/2.0A/4.0A/6.0 A |
|
Charging Voltage |
41.0 VDC ±1% |
| INDICATORS |
| LCD |
Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators |
| ALARM |
| Battery Mode |
Sounding every 4 seconds |
| Low Battery |
Sounding every second |
| Overload |
Sounding twice every second |
| Fault |
Continuously sounding |
| PHYSICAL |
| Standard Model |
Dimension, D x W x H (mm) |
310 x 438 x 88 |
410 x 438 x 88 |
| Net Weight (kgs) |
12 |
14.1 |
| Long-run Model ** |
Dimension, D x W x H (mm) |
310 x 438 x 88 |
| Net Weight (kgs) |
9 |
| ENVIRONMENT |
| Humi dity |
20-90 % RH @ 0- 40°C (No n-condensing) |
| Noise Level |
Less than 50dB @ 1 Meter |
| MANAGEMENT |
| S mart RS-232 / USB |
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux and MAC |
| Optional SNMP |
Power management from SNMP manager and web browser |