Shop

  • MODEL
    Winner Pro+ 1KR(L)

    PHASE
    Single phase with ground

    CAPACITY *
    1000 VA / 900 W

    INPUT

    Nominal Voltage
    110/115/120/127VAC or 208/220/230/240VAC

    Input Voltage Range
    60-145 VAC or 120-300 VAC (Based on load at 50%)
    90-145 VAC or 180-300 VAC (Based on load at 100%)

    Frequency Range
    40 Hz ~ 70 Hz

    Power Factor
    0.99 @ Nominall Voltage (100% load)

    OUTPUT

    Output Voltage
    110/115/120/127VAC or 208/220/230/240VAC

    Voltage Regulation
    ± 1 %

    Frequency Range (Synchronized Range)
    47~ 53 Hz or 57 ~ 63 Hz

    Frequency Range (Batt. Mode)
    50 Hz or 60 Hz ± 0.5%

    Current Crest Ratio
    3:1

    Harmonic Distortion
    3% THD (Linear Load)
    6% THD (Non-linear Load)

    Transfer Time
    AC Mode to Battery Mode
    Zero

    Inverter to Bypass
    4 ms (Typical)

    Waveform (Batt. Mode)
    Pure Sinewave

    EFFICIENCY

    AC Mode
    88%

    Battery Mode
    83%

    BATTERY

    Standard Model
    Battery Type
    12 V / 9 Ah

    Numbers
    2
    3

    Typical Recharge Ti me
    4 hours recover to 90% capacity

    Charging Current ( max.)
    1A

    Charging Voltage
    27.4VDC ± 1%
    41.0VDC ± 1%

    Battery Type
    Depending on applications

    Numbers
    3

    Long-run Model **
    Charging Current ( max.)
    1.0A/2.0A/4.0A/6.0 A

    Charging Voltage
    41.0 VDC ±1%

    INDICATORS

    LCD
    Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators

    ALARM

    Battery Mode
    Sounding every 4 seconds

    Low Battery
    Sounding every second

    Overload
    Sounding twice every second

    Fault
    Continuously sounding

    PHYSICAL

    Standard Model
    Dimension, D x W x H (mm)
    310 x 438 x 88
    410 x 438 x 88

    Net Weight (kgs)
    12
    14.1

    Long-run Model **
    Dimension, D x W x H (mm)
    310 x 438 x 88

    Net Weight (kgs)
    9

    ENVIRONMENT

    Humi dity
    20-90 % RH @ 0- 40°C (No n-condensing)

    Noise Level
    Less than 50dB @ 1 Meter

    MANAGEMENT

    S mart RS-232 / USB
    Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux and MAC

    Optional SNMP
    Power management from SNMP manager and web browser

    Winner Pro Plus Rack 1KR UPS

  • MODEL
    Winner Pro+ 2KR(L)

    PHASE
    Single phase with ground

    CAPACITY *
    2000 VA / 1800 W

    INPUT

    Nominal Voltage
    110/115/120/127VAC or 208/220/230/240VAC

    Input Voltage Range
    60-145 VAC or 120-300 VAC (Based on load at 50%)
    90-145 VAC or 180-300 VAC (Based on load at 100%)

    Frequency Range
    40 Hz ~ 70 Hz

    Power Factor
    0.99 @ Nominall Voltage (100% load)

    OUTPUT

    Output Voltage
    110/115/120/127VAC or 208/220/230/240VAC

    Voltage Regulation
    ± 1 %

    Frequency Range (Synchronized Range)
    47~ 53 Hz or 57 ~ 63 Hz

    Frequency Range (Batt. Mode)
    50 Hz or 60 Hz ± 0.5%

    Current Crest Ratio
    3:1

    Harmonic Distortion
    3% THD (Linear Load)
    6% THD (Non-linear Load)

    Transfer Time
    AC Mode to Battery Mode
    Zero

    Inverter to Bypass
    4 ms (Typical)

    Waveform (Batt. Mode)
    Pure Sinewave

    EFFICIENCY

    AC Mode
    89%

    Battery Mode
    87%

    BATTERY

    Standard Model
    Battery Type
    12 V / 9 Ah

    Numbers
    4

    Typical Recharge Ti me
    4 hours recover to 90% capacity

    Charging Current ( max.)
    1A

    Charging Voltage
    54.7 VDC ±1%

    Long-run Model **
    Battery Type
    Depending on applications

    Numbers
    6

    Charging Current ( max.)
    1.0A/2.0A/4.0A/6.0 A

    Charging Voltage
    82.1 VDC ±1%

    INDICATORS

    LCD
    Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators

    ALARM

    Battery Mode
    Sounding every 4 seconds

    Low Battery
    Sounding every second

    Overload
    Sounding twice every second

    Fault
    Continuously sounding

    PHYSICAL

    Standard Model
    Dimension, D x W x H (mm)
    410 x 438 x 88

    Net Weight (kgs)
    19

    Long-run Model **
    Dimension, D x W x H (mm)
    410 x 438 x 88

    Net Weight (kgs)
    12

    ENVIRONMENT

    Humi dity
    20-90 % RH @ 0- 40°C (No n-condensing)

    Noise Level
    Less than 50dB @ 1 Meter

    MANAGEMENT

    S mart RS-232 / USB
    Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux and MAC

    Optional SNMP
    Power management from SNMP manager and web browser

    Winner Pro Plus Rack 2KR UPS

  • Input:

    • Capacity: 6000 VA / 5400 W
    • Nominal voltage: 208/220/230/240VAC
    • Voltage range: 110-300 VAC at 50% load, 176-300 VAC at 100% load
    • Frequency range: 46Hz  ~ 54Hz or 56Hz ~ 64Hz
    • Power factor: ≥ 0.99 @ nominal voltage (100% load)
      Output:
    • Output voltage: 208/220/230/240VAC   
    • Voltage regulation : ± 1%
    • Frequency range: 46Hz  ~ 54Hz or 56Hz ~ 64Hz
    • Frequency range(Batt. Mode): 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
    • Current crest ratio: 3:1
    • Harmonic distortion (Linear load): ≤ 3% THD
    • Harmonic distortion (non-linear load): ≤ 5% THD
    • Transfer time: 0 ms
    • Waveform (Batt. Mode): Pure sinewave
      Efficiency:
    • AC mode: 92% 
    • Battery mode: 90%
      Battery:
    • Battery type & number: 12 V/9 Ah 
    • Numbers: 16/20
    • Typical recharge time: 9 hours recover to 90% capacity
    • Charging current: 1A/2A (Adjustable)
      Physical:
    • Dimension: D x W x H (mm)(UPS unit): 500 x 438 x 88
    • Dimension: D x W x H (mm)(battery pack): 580x 438 x 133
    • Net weight (kgs)(UPS unit): 15
    • Net weight (kgs)(battery pack): 61
      Environment:
    • Humidity: 0-95 % RH @ 0- 40°C (non-condensing)
    • Noise level: Less than 55dBA @ 1 Meter
      Management:
    • Smart RS-232 / USB: Supports Windows®️ 2000/2003/XP/Vista/2008/Windows®️7/8, Linux, MAC
    • Optional SNMP: Power management from SNMP manager and web browser

     

    Winner Pro Plus Rack 6KR UPS

  • Input:

    • Capacity: 3000 VA / 2700 W
    • Nominal voltage: 110/115/120/127VAC or 208/220/230/240VAC
    • Voltage range:  60-145 VAC  or 120-300 VAC at 50% load, 90-145 VAC or 180-300 VAC at 100% load
    • Frequency range: 40Hz  ~ 70 Hz
    • Power factor: ≥ 0.99 @ nominal voltage (100% load)
      Output:
    • Output voltage: 110/115/120/127VAC or 208/220/230/240VAC   
    • Voltage regulation : ± 1%
    • Frequency range: 47~ 53 Hz or 57 ~ 63 Hz
    • Frequency range(Batt. Mode): 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
    • Current crest ratio: 3:1
    • Harmonic distortion (Linear load): ≤ 3% THD
    • Harmonic distortion (non-linear load): ≤ 6% THD
    • Transfer time: 0 ms
    • Waveform (Batt. Mode): Pure sinewave
      Efficiency:
    • AC mode: 90% 
    • Battery mode: 88%
      Battery:
    • Battery type & number: 12 V/9 Ah 
    • Numbers: 6
    • Typical recharge time: 4 hours recover to 90% capacity
    • Charging current: 1.0A
      Physical:
    • Dimension: D x W x H (mm)(UPS unit): 630 x 438 x 88
    • Dimension: D x W x H (mm)(battery pack): 630 x 438 x 88
    • Net weight (kgs)(UPS unit): 29.3
    • Net weight (kgs)(battery pack): 14.2
      Environment:
    • Humidity: 20-90 % RH @ 0- 40°C (non-condensing)
    • Noise level: Less than 50dBA @ 1 Meter
      Management:
    • Smart RS-232 / USB: Supports Windows®️ 2000/2003/XP/Vista/2008/Windows®️7/8, Linux, MAC
    • Optional SNMP: Power management from SNMP manager and web browser

     

    Winner Pro Plus-Rack 3K-ZR6-R UPS

  • New Design Concept

    Strong Compatibility 

    Independent Core Technology

     

    Features

    • 2600 mAh battery support continuous scanning of 27 hours
    • 2.4G+BT modes, easy to connect with your Pc and mobile devices
    • Good at reading high density and difficult barcodes
    • Easy online upgrade can be finished in several seconds
    • Ideal solution for warehouse and logistics environment using

    WS-630S Wireless Barcode Scanner 2D