Winner Pro Plus Rack 1KR UPS

MODEL Winner Pro+ 1KR(L)
PHASE Single phase with ground
CAPACITY * 1000 VA / 900 W
INPUT
Nominal Voltage 110/115/120/127VAC or 208/220/230/240VAC
Input Voltage Range 60-145 VAC or 120-300 VAC (Based on load at 50%)
90-145 VAC or 180-300 VAC (Based on load at 100%)
Frequency Range 40 Hz ~ 70 Hz
Power Factor 0.99 @ Nominall Voltage (100% load)
OUTPUT
Output Voltage 110/115/120/127VAC or 208/220/230/240VAC
Voltage Regulation ± 1 %
Frequency Range (Synchronized Range) 47~ 53 Hz or 57 ~ 63 Hz
Frequency Range (Batt. Mode) 50 Hz or 60 Hz ± 0.5%
Current Crest Ratio 3:1
Harmonic Distortion 3% THD (Linear Load)
6% THD (Non-linear Load)
Transfer Time AC Mode to Battery Mode Zero
Inverter to Bypass 4 ms (Typical)
Waveform (Batt. Mode) Pure Sinewave
EFFICIENCY
AC Mode 88%
Battery Mode 83%
BATTERY
Standard Model Battery Type 12 V / 9 Ah
Numbers 2 3
Typical Recharge Ti me 4 hours recover to 90% capacity
Charging Current ( max.) 1A
Charging Voltage 27.4VDC ± 1% 41.0VDC ± 1%
Battery Type Depending on applications
Numbers 3
Long-run Model ** Charging Current ( max.) 1.0A/2.0A/4.0A/6.0 A
Charging Voltage 41.0 VDC ±1%
INDICATORS
LCD Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators
ALARM
Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continuously sounding
PHYSICAL
Standard Model Dimension, D x W x H (mm) 310 x 438 x 88 410 x 438 x 88
Net Weight (kgs) 12 14.1
Long-run Model ** Dimension, D x W x H (mm) 310 x 438 x 88
Net Weight (kgs) 9
ENVIRONMENT
Humi dity 20-90 % RH @ 0- 40°C (No n-condensing)
Noise Level Less than 50dB @ 1 Meter
MANAGEMENT
S mart RS-232 / USB Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux and MAC
Optional SNMP Power management from SNMP manager and web browser
Categories: ,