Input:
- Capacity: 6000VA / 5400W 6K(L), 10000 VA / 9000 W 10K(L)
- Nominal voltage: 208/220/230/240 VAC
- Voltage range: 110-300 VAC at 50% load or 176-300 VAC 100% load
- Frequency range: 46~54 Hz or 56~64 Hz
- Power factor: ≥ 0.99 @ nominal voltage (100% load)
Output: - Output voltage: 208/220/230/240 VAC
- Voltage regulation : ± 1%
- Frequency range: 46~54 Hz or 56~64 Hz
- Frequency range(Batt. Mode): 50 Hz or 60Hz ± 0.1 Hz
- Current crest ratio: 3:1
- Harmonic distortion (Linear load): ≤ 3% THD
- Harmonic distortion (non-linear load): ≤ 5% THD
- Transfer time: 0 ms
- Waveform (Batt. Mode): Pure sinewave
Efficiency: - AC mode: 92% 6K(L), 93% 10K(L)
- Battery mode: 90% 6K(L), 91% 10K(L)
Battery: - Battery type & number: 12 V/9 Ah
- Numbers: 16/20
- Typical recharge time: 9 hours recover to 90% capacity
- Charging current: 1A/2A (adjustable)
Indicators: - LCD Panel: UPS status, load level, battery level, input/output voltage, discharge timer, fault conditions
Alarm: - Battery mode: Sounding every 4 seconds
- Low battery Sounding every second
- Overload: Sounding every 0.5 second
- Fault: Continuously sounding
Physical: - Dimension: D x W x H (mm)(UPS unit): 369 x 190 x 688 6K(L), 442 x 190 x 688 10K(L)
- Dimension: D x W x H (mm)(battery pack): 369 x 190 x 318 6K(L), 442 x 190 x 318 10K(L)
- Net weight (kgs)(UPS unit): 61 6K(L), 74 10K(L)
- Net weight (kgs)(battery pack): 12 6K(L), 16 10K(L)
Environment: - Humidity: 0-95 % RH @ 0-50°C (Non-condensing) 6K(L), 0-95 % RH @ 0-50°C (Non-condensing) 10K(L)
- Noise level: less than 55 dB 6K(L), less than 55 dB 10K(L)
Management: - Smart RS-232 / USB: Supports Windows®️ 2000/2003/XP/Vista/2008/Windows®️7/8, Linux, MAC
- Optional SNMP: Power management from SNMP manager and web browser