LAN Cable CAT6 F/UTP 4x2x23 AWG Outdoor
Application:
PBX, V.11, X.21, ISDN, Ethernet (10Base-T), ATM-25/52/155 Mbit/s, 100VG-AnyLAN, Fast Ethernet (100BASE-TX), Token Ring 16/100 Mbit/s, Firewire 100 Mbit/s, PoE (IEEE 802.3af), PoE+ (IEEE 802.3at), PoE++ (IEEE 802.3bt), HDBaseT, 1000BASE-T, 2.5GBASE-T, 5GBASE-T, 10GBASE-T (under 55 m)
Installation and Operation conditions:
For outdoor installation in telephone ducts, collectors, mines, on the walls of buildings in conditions of heightened electro-magnetic impacts. Operated on frequencies up to 250 MHz
Compliance with the requirements:
Cabling: ISO/IEC 11801-1, EN 50173-1, ANSI/TIA-568-C.2
Cable: IEC 61156-5, EN 50288-5-1
Mechanical characteristics:
Temperature range:
- During installation -10 °C … +60 °C
- After installation -50 °C … +60 °C
Bending radius:
- During installation ≥ 8 cable diameters
- After installation ≥ 4 cable diameters
Tensile stress ≤ 85 N
Electrical characteristics at 20 °C:
Parameter | Unit | Value |
Capacitance | pF/m | ≤ 56 |
Direct current resistance | Оhm/km | ≤ 85 |
Insulation resistance | GOhm/km | ≥ 5 |
Resistance unbalance | % | 2 |
Signal propagation velocity | s | 0,68 |
Propagation delay | ns/100 m | ≤ 534+36/√f |
Delay shift on the frequency 100 MHz | ns/100 m | ≤ 30 |
Characteristic impedance in the frequency range of:
1-100 MHz 100-250 MHz |
Ohm |
100±15 100±22 |
Test voltage between cores, (DC, 2 s) | kV | 2,5 |
Frequency, MHz | 1 | 4 | 10 | 16 | 20 | 31,25 |
Attenuation, dB, max | 2,1 | 3,8 | 6 | 7,6 | 8,5 | 10,8 |
NEXT, dB, min | 75,3 | 66,3 | 60,3 | 57,3 | 55,8 | 52,8 |
PS NEXT, dB, min | 72,3 | 63,3 | 57,3 | 54,3 | 52,8 | 49,8 |
ELFEXT, dB, min | 68 | 56 | 48 | 44 | 42 | 38 |
PS ELFEXT, dB, min | 65 | 53 | 45 | 41 | 39 | 35 |
RL, dB, min | 20,0 | 23,0 | 25,0 | 25,0 | 25,0 | 23,6 |
Frequency, MHz | 62,5 | 100 | 250 |
Attenuation, dB, max | 15,5 | 19,9 | 33 |
NEXT, dB, min | 48,3 | 45,3 | 39,3 |
PS NEXT, dB, min | 45,3 | 42,3 | 36,3 |
ELFEXT, dB, min | 32 | 28 | 20 |
PS ELFEXT, dB, min | 29 | 25 | 17 |
RL, dB, min | 21,5 | 20,1 | 17,3 |
IEC 61156-5, values lower than 4 MHz are given for information only