LAN Cable CAT 5 U/UTP 2x2x24 AWG indoor

Application

PBX, V.11, X.21, ISDN, Ethernet (10Base-T), ATM-25/52/155 Mbit/s, 100VG-AnyLAN, Fast Ethernet (100BASE-TX), Token Ring 16/100 Mbit/s

Installation and Operation Conditions

For outdoor installation in telephone ducts, collectors, mines, on the walls of buildings in conditions of heightened electro-magnetic impacts.
Operated on frequencies up to 250 MHz

Compliance with the requirements

Cabling: ISO/IEC 11801-1, EN 50173-1, ANSI/TIA-568-C.2

Cable: IEC 61156-2

Mechanical Characteristics

Temperature range:    During installation -10 °C … +60 °C

After installation -20 °C … +60 °C

Bending radius:            During installation ≥ 8 cable diameters

After installation ≥ 4 cable diameters

Tensile stress ≤ 85 N

 

ELECTRICAL CHARACTERISTICS AT 20 °C

Parameter Unit Value
Capacitance pF/m ≤ 56
Direct current resistance Оhm/km ≤ 95
Insulation resistance GOhm/km ≥ 5
Resistance unbalance % 2
Signal propagation velocity s 0,68
Propagation delay ns/100 m ≤ 534+36/√f
Delay shift on the frequency 100 MHz ns/100 m ≤ 30
Characteristic impedance in the frequency range of:

1-100 MHz

 

Ohm

 

100±15

Test voltage between cores, (DC, 2 s) kV 2,5

 

Frequency, MHz 1 4 10 16 20
Attenuation, dB, max: 2,1 4,1 6,5 8,3 9,3
NEXT, dB, min 65,3 56,3 50,3 47,2 45,8
ELFEXT, dB, min 64 52 44 40 38
RL, dB, min 20,0 23,0 25,0 25,0 25,0
Frequency, MHz 31,25 62,5 100
Attenuation, dB, max: 11,7 17,0 22,0
NEXT, dB, min 42,9 38,4 35,3
ELFEXT, dB, min 34 28 24
RL, dB, min 23,3 20,7 19,0

IEC 61156-5, values lower than 4 MHz are given for information only

 

Categories: , ,