Cable Design:
Conductor – Solid bare copper wire
Diameter – Ø 0,80 mm
Insulation – Polyvinylchloride (PVC)
Diameter – Ø 1,60 mm
Formation –4 wires twisted to a squad
Pair identification – Red, Yellow, White, Black
Tape – Plastic tape overlapped
Drain Wire – Copper wire
Diameter – Ø 0,40 mm
Screen – Alulaminate foil overlapped
Coverage – 100%’
Outer Jacket –Polyvinylchloride (PVC), Red (RAL 3000)
Diameter – Ø 5,6 mm
Application
Cable PVC for building system technology to control lighting, heating, air-conditioning, ventilation, energy management, blinds, time management and locking systems. Not to be layed in ground.
Electrical Data @20 C
Loop resistance (max.) | 73,20 Ohm/km |
Insulation resistance (min.) | 100 MOhm*km |
Operating Capacity (max.) | 100 nF/m |
k1 : Capacitance unbalance (max.) | 200 pF/100m |
Test Voltage : core-shield | 4 kV 50 Hz 1min. |
Peak Operating Voltage | 300 V |
Mechanical & Thermal Characteristics
Flame retardant | acc. to IEC 60332-1-2 |
Temperature Range | during installation : -5 C up to +50 C |
static : -30 C up to +70 C | |
Weight (approx.) | 58 kg/km |