Outdoor UPS is designed for extreme demanding environments where clean backup power is needed. Built-in with AVR function, it helps to maintain normal operation without transferring to battery mode during voltage surge or sag. It also offers battery temperature sensor connector to monitor connected battery temperature anytime. Equipped with dry contacts, outdoor UPS is able to provide programmable signals for event alarms. It’s perfect to use in security, communication, traffic and many other critical industrial environments.

Main Features
  • Provides continuous power to critical loads during blackout in rugged environment
  • Wide operating temperature range from -40°C to 80°C suits for outdoor applications
  • Built-in boost and buck AVR to regulate input voltage
  • Selectable transfer time for normal or generator modes
  • Provides RS-232, USB and SNMP intelligent port
  • Circuit breaker protection on AC input, AC output and external battery input
  • User-adjustable charging current
  • Adjustable input threshold voltage
  • Provides programmable signals for dry contacts
  • Battery compensation design will optimize battery lifecycle
Model Outdoor 2000A
RATED POWER 2000VA/1600W
INPUT
Nominal Voltage120 VAC or 230 VAC
Acceptable Voltage Range100-130 VAC (Default) or 170-300 VAC 88-152 VAC (AVR Function enabled only available for 120VAC system, adjustable)
Frequency Range50 Hz/60 Hz (Auto sensing)
OUTPUT
Nominal Voltage120 VAC or 230 VAC
Voltage Regulation (Batt. Mode)120 VAC ± 5% or 230 VAC ± 5%
Frequency50Hz/60Hz ± 0.1%
THD (Batt. Mode)<3% @ Full resistive load
EfficiencyAC Mode95%
AVR Mode90%
Battery Mode87% - 90%
Transfer TimeNormal Mode (max.)12ms
Generator Mode (max.)25ms
WaveformPure sinewave
BATTERY
Nominal DC Voltage48VDC
Low DC Warning Voltage46VDC ± 0.4VDC @ no load
Battery TypeAGM/Gel
Charging Current2A/4A/6A/8A/10A (Adjustable)
INDICATORS
Bypass ModeGreen LED on
Battery ModeGreen LED flashing
No OutputGreen LED Off
Warning with OutputYellow LED on
Fault without OutputRed LED on
MANAGEMENT
CommunicationRS-232/USB and SNMP
Dry Contact Rating 3A @ 125VAC or 250VAC
PHYSICAL
Dimension, D x W x H (mm)400 x 240 x 133
Net Weight (kgs)12.5
Type of Mechanical ProtectionIP20
OPERATING ENVIRONMENT
Humidity 5% to 95% Relative Humidity (Non-condensing)
Operating Temperature-40℃ to 80℃
Noise Level< 48dB
COMPLIANCE
EMI ComplianceClass A FCC/CISPR [EN50091-2: 1995]
Surge ProtectionIEEE/ANSI C.62.41 & 2KV, L-N
No downloads available
top